Overview of the PoE+ settings of a Linksys Managed PoE+ Gigabit Switch

The PoE+ settings page of your Linksys Managed PoE+ Gigabit Switch contains PoE subsystem information for monitoring the current power usage and assigns the total amount of power the switch can provide to all of its PoE+ ports.  To access this page, follow the steps below:
 
Step 1:
Access the web interface of your switch.  For instructions, click here.

Step 2:
Click on PoE+ under the System menu.

NOTE:  Options may differ depending on the model number of your switch.
 
User-added image

Below are settings which can be configured under the PoE+ page:

Power Budget
PoE+ Port Settings
 

  Power Budget
 
  • Total Power Budget:  Allows you to enter the amount of power the switch can provide to all ports.
  • Consumed Power:  Displays the total amount of power (in Watts) that’s currently being delivered to all PoE+ ports.
 
NOTE:  The total power budget will differ for every Linksys Managed PoE+ Gigabit Switch.

User-added image

Make sure to click on Apply to save your settings.

PoE+ Port Settings

To see more columns (left or right), click on the blue  arrows.  After changing your port settings, make sure to scroll down and click Apply to save your settings.
 
User-added image
 
  • Port:  Displays the specific port number for which PoE parameters are defined.  PoE parameters are assigned to the powered device that is connected to the selected port.
  • State:  Disable or enable PoE on the port.  By default, all ports are PoE-enabled.
  • Priority:  Select the port priority if the power supply is Low.  The default is Medium.  For example, if the power supply is running at 99% usage, and port 1 is prioritized as High, but port 6 is prioritized as Low, port 1 is prioritized to receive power and port 6 may be denied power.
 
  • Low:  Sets the PoE priority level as low.
  • Medium:  Sets the PoE priority level as medium.
  • High:  Sets the PoE priority level as high.
  • Critical:  Sets the PoE priority level as critical.
 
  • Power Limit Type:  Shows the classification of the connected powered device.  The class defines the maximum power that can be provided to the powered device. 
 
To change the Power Limit Type, first select a port, click the drop down to select Auto Class at the top of the column or User defined, if needed manually set a user power limit and click Apply.

The possible field values are:

 
  • Class 0:  The maximum power level at the Power Sourcing Equipment is 15.4 Watts.
  • Class 1:  The maximum power level at the Power Sourcing Equipment is 4.0 Watts.
  • Class 2:  The maximum power level at the Power Sourcing Equipment is 7.0 Watts.
  • Class 3:  The maximum power level at the Power Sourcing Equipment is 15.4 Watts.
  • Class 4:  The maximum power level at the Power Sourcing Equipment is 30 Watts.
  • Class:  Select this option to base the power limit on the value configured in the User Power Limit field.
  • Auto Class:  Auto Class means the power limit is based on the class, which PSD (switches) detects on the PD device.
 
  • User defined (W):  Select this option to base the power limit on the value configured in the User Power Limit field.
  • Status:  Shows the port's PoE status.
 
The possible field values are:
 
  • Delivering Power:  The device is enabled to deliver power via the port.
  • Disabled:  The device is disabled for delivering power via the port.
  • Test Fail:  The powered device test has failed.  For example, a port could not be enabled and cannot be used to deliver power to the powered device.
  • Testing:  The powered device is being tested.  For example, a powered device is tested to confirm if it is receiving power from the power supply.
  • Searching:  The device is currently searching for a powered device.  Searching is the default PoE operational status.
  • Fault:  The device has detected a fault on the powered device when the port is forced on.  For example, the power supply voltage is out of range, a short circuit occurs, a miscommunication or a communication error with a PoE device, or an unknown error occurs.